any type of surge that could damage your expensive equipment. Ideal for your heavy-duty equipment, it can also be applicable to your intelligent equipment with soft start ability.
KEY FEATURES
- Phase: Three Phase + N + GNaD
- Output Voltage: 380V
- Over-voltage Protection; Low-voltage Protection
- Display Model: LED / METER
- Wide Input Voltage Range: 277V ~ 433V
- 6 Steps Transformer Design In Voltage Stabilizing – For that extra reliability
- Voltage Protection – High / Low Voltage, High Temperature Protection
- Soft Start Protection – Safeguards your expensive equipments
- Ideal for heavy-duty equipment
Specifications
Capacity 15 KVA
AC INPUT
Voltage range 277 V ~ 433 V
Frequency range 50/60 Hz
Phase Three-phase+ N + G
AC OUTPUT
Voltage: 380 V / 400 V / 415 V
Voltage: regulation accuracy  ± 3%
Waveform:Â Sinusoidal
Efficiency: 96%
Power factor: 0.8
Distortion: No additional waveform distortion
Response time: ± 10% varies< 1 s
Over-voltage protection: Output phase voltage 433 V ± 5 V
Under-voltage: Output phase voltage 316 V ± 5 V
Other protections: Start-up delay -mechanical failure -over-current -short-circuit -phase order (three-phase) -lack-phase (three-phase) -over temperature
There are no reviews yet.